Worked examples — Use Norton equivalent circuits
The scenario matrix
Before working anything, let's list every case class a Norton problem can belong to. Each worked example below is tagged with the cell it fills.
| Cell | Case class | What makes it tricky | Example |
|---|---|---|---|
| A | Single voltage source, series–parallel resistors | baseline recipe | Ex 1 |
| B | Single current source | source stays as current, deactivate = open | Ex 2 |
| C | Two independent sources | use Superposition or nodal for | Ex 3 |
| D | Dependent source present | can't kill it; test-source for | Ex 4 |
| E | Degenerate: short-circuit branch () | , model becomes ideal source | Ex 5 |
| F | Degenerate: open branch / no source | or | Ex 6 |
| G | Sign case: negative / reversed-polarity load | apply the terminal law with signs | Ex 7 |
| H | Active negative (strong dependent source) | test source gives | Ex 8 |
| I | Word problem + Maximum power transfer () | translate words → circuit, compute | Ex 9 |
| J | Exam twist: find by the method | two-measurement shortcut | Ex 10 |
The signs to watch: a current source can push current the "wrong" way through the short (negative , Ex 7), and a strong dependent source can make the terminal slope run backwards (negative , Ex 8). Both are worked below.
Cell A — baseline: one voltage source

- Short a–b, find . Placing a wire across a–b joins both ends of , so carries and is invisible. Only limits the source: Why this step? A short forces terminal voltage , and the terminal law gives . The short reads off directly.
- Kill the source, find . Replace with a wire. Now the tops of and are tied together and both hang between the same two nodes a–b — they are in parallel: Why this step? is the slope of the – line, set purely by resistors (Ohm's Law); sources only shift the line, so we switch them off to isolate it.
- Draw .
Verify: cross-check with Thévenin equivalent circuits. Open-circuit voltage should be . Independently: with a–b open, the terminal draws nothing, so carries the full source current and . ✓ Match.
So exactly as the forecast's "hold that thought" hinted — vanished under the short.
Cell B — a current source instead
- Short a–b, find . A wire across a–b gives a path in parallel with both and . All prefers the wire (zero resistance), so: Why this step? Any resistor in parallel with a short is bypassed — the entire source current flows through the short. The current source hands its whole to the short.
- Deactivate the source, find . For a current source, "off" means open (a gap) — a current source that pushes zero current is an open circuit. With that gap, and both bridge a–b in parallel: Why open, not short? Shorting a current source would create a second loop and misread the resistance. Opening it removes its influence while leaving the resistor network intact.
- Draw .
Verify: . Independently with a–b open, the splits through , giving . ✓ Units: A·Ω = V. ✓
Forecast answered: barely any work — a current source is the answer once you route it through the short.
Cell C — two sources at once

- Short a–b, find by Superposition. The short holds node a at , so (also across a–b) carries no current — ignore it. Each source drives its own branch straight into the short: Why superposition? In a linear network the short-circuit current is the sum of what each source alone would push through the short (Kirchhoff's Current Law at the shorted node). Both sources point current into a and out the short, so they add.
- Kill both sources, find . Replace both voltage sources with wires. Now , , all connect a to b (their far ends are all grounded through the wires) — three resistors in parallel: Why this step? Deactivating both sources ties every resistor's far end to the same rail, so all three bridge a–b.
- Draw .
Verify: . Independent nodal check with a–b open, at node a: ✓
Forecast confirmed: the two short-circuit currents added to .
Cell D — a dependent source
- Short a–b, find . Short forces , so , so the dependent source contributes nothing. Only the source drives the short through : Why this step? The dependent source is controlled by ; the short zeroes , silencing it. is shorted out too, so alone sets the short-circuit current.
- Find with a test source — do NOT deactivate the dependent source. Why this step? A dependent source has no independent "on/off" — its output tracks , which we are about to change. You cannot switch off something that only reacts. So we kill only the independent source (→ wire), then apply a known test voltage at a–b and measure the current it draws; their ratio is the resistance the dependent source helps define. With the independent source off, , , and KCL at node a (current out through resistors minus current injected by the dependent source ): The dependent source's minus sign here reduces , raising above the plain .
- Draw .
Verify: should equal . Independent open-circuit nodal at a (no load current): . ✓
Cell E — degenerate: a short across the terminals of a source
- Short a–b, find . Shorting an ideal voltage source demands across a device that insists — the model gives infinite current. This is a degenerate case: a pure ideal voltage source has no finite Norton current. Why? and here , so . The Norton form breaks down.
- Kill the source, find . Replace with a wire: terminals a–b are joined directly, so
- Interpretation: an ideal voltage source is the limit — it has a perfect Thévenin equivalent circuits () but no proper Norton equivalent (you'd need ). Add any real series resistance and it recovers: , .
Verify: with added, , , and . ✓ As , — confirms the degeneracy.
Cell F — degenerate: no source, or an open branch (apply the terminal law)
- (F1) Short a–b, find . No source ⇒ no drive ⇒ no current: . Kill "sources" (there are none), find . Result: — this is just a resistor (a dead network is a pure resistor). ✓ sanity: a resistor's – line passes through the origin, so intercept .
- Apply the terminal law . Attach a source externally across a–b (so is forced) and predict the current the network absorbs: Why the minus? is defined as current delivered by the network. A dead resistor delivers nothing; instead it draws , which shows up as a negative . This is the terminal law doing real work, not decoration.
- (F2) Open branch. The switch open isolates the source from a–b. Shorting a–b draws ; with no resistor path to the terminals, (an open circuit). The terminal law then gives, for any : Why ? An open circuit is the limit; no current flows no matter the applied voltage — correct for isolated terminals.
Verify: (F1) — a dead network shows no open-circuit voltage. ✓ Terminal-law prediction: across draws (magnitude), so . ✓ (F2) for any . ✓
Cell G — a sign case: negative and a reversed-polarity load
- Short a–b, find . With a wire across a–b, the source's is forced through the short — but it flows into terminal a and out the source, i.e. into the box, which is the negative direction for (defined as current leaving a through the short toward the load): Why negative? 's sign encodes direction. A source that drains the terminal produces a short-circuit current pointing the opposite way — the minus sign carries that physics. is shorted out and irrelevant here.
- Kill the source (open it), find . Only bridges a–b:
- Attach ; apply the terminal law. The Norton source feeds a divider; equivalently, with across the model the terminal voltage satisfies and . Solve together: The negative means current actually flows into terminal a from the load side — a reversed-polarity delivery. The load voltage is : terminal a sits below b. Why carry the sign through? Flipping to "magnitude 2 A" hides that the box is absorbing, not sourcing. The sign is the answer's most important digit.
Verify: plug back into the terminal law: . ✓ Self-consistent, and . ✓ Units: A·Ω = V. ✓
Forecast confirmed: a draining source gives a negative , and the terminal law propagates that sign cleanly into a reversed-polarity load.
Cell H — active network: a negative Norton resistance
- Apply a test source. Force at a, so . KCL at node a (current out through minus current injected by the dependent source ): Why this step? No independent source and a dependent source ⇒ the only way to read the terminal slope is to probe with a known and see the response .
- Compute . Why negative? The dependent source pumps more current into node a () than can drain () at , so raising the terminal voltage makes the network push current back out — the – slope runs backwards. A negative is the signature of an active network (it can deliver power indefinitely, like an oscillator's negative-resistance stage).
- Interpretation. The Norton model still holds formally: with . But this network is not passive — connect the wrong load and it may not settle. That is exactly why exam problems flag "check the sign of ".
Verify: self-check the KCL: at , out through is ; injected is ; net drawn , so . ✓ Sign is negative ⇒ active network. ✓
Cell I — real-world word problem + maximum power
-
(a) : short the sensor terminals. The battery drives its EMF through + cable in series: Why this step? Shorting the terminals () makes the battery push its full current through the total series resistance.
-
: kill the battery EMF. Replace the EMF with a wire; the internal and cable resistances remain in series:
-
(b) Max power transfer. Power in is maximised when (Maximum power transfer).
Matched load current and power: Equivalently, the standard closed form agrees. Why match? Too small an and voltage collapses; too large and current starves. The sweet spot is , giving .
Verify: Power in at match: too, so efficiency . ✓ Forecast: matching gives exactly half the power to the load, not most of it. ✓ Both formulas give . ✓ Units: A²·Ω = W. ✓
Cell J — exam twist: from two measurements
- is the short-circuit current — read directly. Why this step? is defined as the terminal current when shorted. The ammeter measured exactly that.
- from the ratio of the two readings. Both meters probe the same – line. Open circuit gives ; solve for : Why this step? The line runs from intercept to ; its slope magnitude is . This is the professional way to measure without opening the box or knowing internal sources.
- Draw , equivalently Thévenin equivalent circuits .
Verify: self-consistency: ✓ and ✓. Attach : , load voltage — exactly half of , the matched-load signature. ✓
Recall Self-test across the whole matrix
One current source () alone across : what is ? ::: — the whole source current takes the short. Two voltage sources and into a shorted node: ? ::: by superposition. A current source that drains terminal a with : ? ::: — the sign flips because current enters the box. Test source gives at : ? ::: — an active (negative-resistance) network. Matched load on : ? ::: . An ideal source with no series resistance: does a Norton equivalent exist? ::: No — forces ; add series to fix. Black box reads , : ? ::: . With a dependent source present, how do you get ? ::: Kill only independent sources, apply a test source, .
Connections
- Use Norton equivalent circuits — the parent recipe these examples exercise.
- Superposition — used in Ex 3 to add short-circuit currents.
- Kirchhoff's Current Law — the node law behind every .
- Ohm's Law — every and -combination.
- Thévenin equivalent circuits & Source transformation — the bridge and cross-checks.
- Maximum power transfer — the matched-load result in Ex 9.